MAGNETIC STARTER COMBINATION TABLE |
| D.O.L. Magnetic Starter |
KW |
0.18 |
0.37 |
0.55 |
0.75 |
1.1 |
1.5 |
2.2 |
3 |
3.7 |
5.5 |
7.5 |
11 |
15 |
18.5 |
22 |
| HP |
1/4 |
1/2 |
3/4 |
1 |
1.5 |
2 |
3 |
4 |
5 |
7.5 |
10 |
15 |
20 |
25 |
30 |
SINGLE
PHASE
220V
50/60Hz |
MOTOR FULL LOAD CURRENT
A |
2.30 |
4.10 |
5.00 |
6.75 |
9.50 |
11.3 |
14.5 |
- |
24.5 |
|
|
|
|
|
|
| MAGNETIC
CONTACTOR (MC) C- |
11L |
11L |
11L |
11L |
16L |
16L |
16L |
- |
25L |
|
|
|
|
|
|
| THERMAL OVERLOAD RELAY (TOR) RH- |
10 |
10 |
10 |
10 |
10 |
10 |
18 |
- |
18 |
|
|
|
|
|
|
| RATED OVERLOAD CURRENT
A |
3 |
4 |
5 |
7 |
10 |
13 |
15 |
- |
26 |
|
|
|
|
|
|
| MOLDED
CASE CIRCUIT BREAKER |
30S |
30S |
30S |
30S |
30S |
30S |
30S |
- |
50S |
|
|
|
|
|
|
(MCCB) |
50E |
| MCCB
RATED CURRENT (AMPERE) A |
15 |
15 |
15 |
15 |
15 |
20 |
20 |
- |
40 |
|
|
|
|
|
|
THREE
PHASE
440V
50/60Hz |
MOTOR
FULL LOAD CURRENT A |
0.65 |
1.0 |
1.4 |
1.8 |
2.6 |
3.4 |
4.9 |
6.5 |
7.6 |
11.2 |
14.5 |
21 |
27 |
34 |
40 |
| MAGNETIC
CONTACTOR (MC) C- |
11L |
11L |
11L |
11L |
11L |
11L |
11L |
11L |
11L |
16L |
18L |
20L |
25L |
35L |
35L |
| THERMAL OVERLOAD RELAY (TOR) RH- |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
18 |
18 |
18 |
35 |
35 |
| RATED OVERLOAD CURRENT
A |
0.55 |
1.2 |
1.2 |
1.7 |
3 |
3 |
5 |
7 |
7 |
13 |
15 |
20 |
26 |
30 |
42 |
| MOLDED
CASE CIRCUIT BREAKER |
30S |
30S |
30S |
30S |
30S |
30S |
30S |
30S |
30S |
30S |
50S |
50S |
50S |
100S |
100S |
(MCCB) |
50E |
50E |
50E |
100E |
100E |
| MCCB
RATED CURRENT (AMPERE) A |
15 |
15 |
15 |
15 |
15 |
15 |
15 |
20 |
20 |
30 |
40 |
40 |
50 |
60 |
75 |